Cummins, Inc. recalls 2015–2018 Cummins Power Generation Generator Set
- Recall date
- July 31, 2018
- Source
- National Highway Traffic Safety Administration (NHTSA)
- Recall number
- 18V504000
- Brand / firm
- Cummins Power Generation
- Sold / distributed
- Potentially affected: 921 units
Why it was recalled
If the unit does not shut down as expected when the remote E-stop is activated, it can increase the risk of injury.
What was recalled
Cummins Inc. (Cummins) is recalling certain 2015-2018 Power Generation trailers, models C60D6R, C150D6R, C80D6R, C100D6R, C200D6R, C300D6R, C150D2R3 and C200D2Re, 2016-2018 C275D2Re and 2018 C70D2Re and C100D2Re. These generator sets may have incorrectly wired remote emergency stop and remote start connections causing the remote stop to not function and shut down the generator as intended.
What to do
Cummins will notify owners, and dealers will inspect the remote E-stop function and, if necessary, repair or replace the remote E-stop/remote start switch panel, free of charge. The recall is expected to begin September 2018. Owners may contact Cummins customer service at 1-800-286-6467.. Follow the official notice for full instructions.
Read the official recall notice →
Get recall alerts
Free email alert whenever Cummins Power Generation has a new recall — straight from official government data. Unsubscribe anytime.
More recalls from: Cummins Power Generation