Philips Network Firewall recalled over fire hazard
- Recall date
- October 5, 2017
- Source
- U.S. Food & Drug Administration (FDA) — enforcement report
- Official notice title
- Philips Electronics North America Corporation recalls Philips Network Firewall (Cisco ASA 5506), Model # 867098
- Recall number
- Z-0850-2018
- FDA classification
- Class II
- Brand / firm
- Philips Electronics North America Corporation
- Sold / distributed
- US Nationwide
Why it was recalled
Firewall installed with Philips IntelliVue Information Center iX or Information Center Classic may have a defective component, which may result in loss of connection to the Information Center iX. The defect involves the clock signal component within the firewall. This component has a high probability of failing in appliances that have been running for greater than 18 months. If the clock signal component were to fail, the firewall will stop functioning, will not boot, and is not recoverable. This failure will result in loss of communication between devices that are separated by the firewall, which may cause the Information Center to reboot.
Class II means using this product may cause temporary or medically reversible health problems; the chance of serious harm is remote.
What was recalled
Philips Network Firewall (Cisco ASA 5506), Model # 867098
Get recall alerts
Free email alert whenever Philips Electronics North America Corporation has a new recall — straight from official government data. Unsubscribe anytime.
More recalls from: Philips Electronics North America Corporation